New York Codes Rules Regulations (Last Updated: March 27,2024) |
![]() |
TITLE 12. Department of Labor |
![]() |
Chapter I. Industrial Board of Appeals |
![]() |
Subchapter A. The Industrial Code |
![]() |
Part 14. Construction, Installation, Inspection and Maintenance of High Pressure Boilers; Construction of Unfired Pressure Vessels |
![]() |
Subpart 14-9. Power Boilers: New Installations |
![]() |
Safety Valves and Safety Relief Valves |
Sec. 14-9.8. Stamping of valves
Latest version.
- Each safety valve or safety relief valve shall be plainly marked by the manufacturer in such a way that the markings will not be obliterated in service. The markings may be stamped on the casing, or stamped or cast on a plate or plates securely fastened to the casing, and shall contain the following markings:(a) The name or identifying trademark of the manufacturer.(b) Manufacturer's design or type number.(c) Size _ in. Seat diameter _ in.(The pipe size of the valve inlet.)(d) Pressurelb.(The steam pressure at which it is to blow.)(e) Year built, or alternatively, a coding may be marked on the valve such that the valve manufacturer can identify the year built.(f) Capacitylb. per hr.(In accordance with sections 14-9.9 and 14-9.12 of this Subpart.)(g) Capacity liftin.(Capacity lift-distance the valve disk rises under the action of the steam when the valve is blowing under a pressure of three percent above the set pressure.)(h) ASME symbol.