Subpart 4-11. Flame Safeguard Control Requirements for All Oil Burners Installed Before March 31, 1965 |
Sec. 4-11.3. Manual—maximum firing rate over seven gallons per hour
Latest version.
- After the burner is manually lit the main flame shall be continually supervised while the burner is firing. The electrical circuit to the main fuel valve shall be automatically de-energized within four seconds after flame failure and the de-energized valve shall automatically close within the next five seconds.