Sec. 4-12.3. Manual or automatic—maximum firing rate three gallons per hour or less  


Latest version.
  • On all manual or automatic oil-fired boilers having a firing rate of three gallons per hour or less, the main flame trial-for-ignition period shall not exceed 90 seconds. Upon flame failure, the main oil valve shall close automatically within 90 seconds.