New York Codes Rules Regulations (Last Updated: March 27,2024) |
![]() |
TITLE 12. Department of Labor |
![]() |
Chapter I. Industrial Board of Appeals |
![]() |
Subchapter A. The Industrial Code |
![]() |
Part 4. Low Pressure Boilers |
![]() |
Subpart 4-12. Flame Safeguard Control Requirements for Oil Burners Installed After March 31, 1965 |
Sec. 4-12.3. Manual or automatic—maximum firing rate three gallons per hour or less
Latest version.
- On all manual or automatic oil-fired boilers having a firing rate of three gallons per hour or less, the main flame trial-for-ignition period shall not exceed 90 seconds. Upon flame failure, the main oil valve shall close automatically within 90 seconds.