New York Codes Rules Regulations (Last Updated: March 27,2024) |
![]() |
TITLE 12. Department of Labor |
![]() |
Chapter I. Industrial Board of Appeals |
![]() |
Subchapter A. The Industrial Code |
![]() |
Part 4. Low Pressure Boilers |
![]() |
Subpart 4-12. Flame Safeguard Control Requirements for Oil Burners Installed After March 31, 1965 |
Sec. 4-12.4. Manual—maximum firing rate over three gallons per hour
Latest version.
- After the burner is manually lit, the main flame shall be continually supervised while the burner is firing. The electrical circuit to the main fuel valve shall be automatically de-energized within four seconds after flame failure and the de-energized valve shall automatically close within the next five seconds.