Sec. 4-13.2. Boiler openings  


Latest version.
  • (a) Openings required.
    Boiler openings must meet the requirements of section IV of the ASME Code.
    (b) Threaded openings.
    All threaded openings in a boiler shall be tapped into material having a minimum thickness as specified for the various standard pipe sizes in the following table:
    MINIMUM THICKNESS OF MATERIAL FOR TAPPINGS
    Pipe sizeMinimum thickness of material or length of thread required
    (inches)(inches)
    1 and under¼
    1¼ to 2, inclusive/16
    /16
    3 to 3½, inclusive
    4 to 5, inclusive
    6 to 8, inclusive1
    9 to 12, inclusive